Cyber Resilience

CVE-2025-30002

High

Published: 16 April 2025

Published
16 April 2025
Modified
19 August 2025
KEV Added
Patch
CVSS Score v4 8.7 CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
EPSS Score 0.0008 23.3th percentile
Risk Priority 17 60% EPSS · 20% KEV · 20% CVSS

Summary

CVE-2025-30002 is a high-severity SQL Injection (CWE-89) vulnerability in Siemens Telecontrol Server Basic. Its CVSS base score is 8.7 (High).

Operationally, ranked at the 23.3th percentile by exploit likelihood (below the median); it is not currently listed in the CISA KEV catalog.

Deeper analysis

TeleControl Server Basic versions prior to V3.1.2.2 contain a SQL injection vulnerability in the internally used UpdateConnectionVariables method, tracked as CWE-89. The flaw permits an authenticated remote attacker who can reach TCP port 8000 to bypass authorization checks, read from and write to the application's database, and execute code under the NT AUTHORITY\NetworkService account.

An attacker with valid credentials on a reachable instance can leverage the injection to manipulate database contents and escalate to operating-system-level code execution without user interaction. The CVSS 4.0 score of 8.7 reflects network attack vector, low attack complexity, and high impact on confidentiality, integrity, and availability.

The Siemens advisory SSA-443402 recommends upgrading to version 3.1.2.2 or later to remediate the issue.

EPSS for the CVE rose from a low of 0.0008 to a peak of 0.0100, indicating emerging exploitation interest after disclosure.

EU & UK References

Vulnerability details

A vulnerability has been identified in TeleControl Server Basic (All versions < V3.1.2.2). The affected application is vulnerable to SQL injection through the internally used 'UpdateConnectionVariables' method. This could allow an authenticated remote attacker to bypass authorization controls, to read…

more

from and write to the application's database and execute code with "NT AUTHORITY\NetworkService" permissions. A successful attack requires the attacker to be able to access port 8000 on a system where a vulnerable version of the affected application is executed on. (ZDI-CAN-25909)

CWE(s)

Related Threats

No named actor attribution yet. ATT&CK technique mapping in progress for this CVE.

Affected Assets

siemens
telecontrol server basic
≤ 3.1.2.2

Mitigating Controls

Likely Mitigating Controls AI

Per-CVE control mapping for this CVE has not run yet; the list below is derived from the weakness types (CWEs) cited in the NVD entry.

addresses: CWE-89

Penetration testing uses SQL injection payloads against database interfaces, identifying and supporting fixes for SQL injection weaknesses.

addresses: CWE-89

Validates query inputs to prevent SQL syntax or command manipulation.

References