Cyber Resilience

CVE-2021-27196

High

Published: 14 June 2021

Published
14 June 2021
Modified
21 November 2024
KEV Added
Patch
CVSS Score v3.1 7.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
EPSS Score 0.0104 77.9th percentile
Risk Priority 16 60% EPSS · 20% KEV · 20% CVSS

Summary

CVE-2021-27196 is a high-severity Improper Input Validation (CWE-20) vulnerability in Hitachienergy Relion 670 Firmware. Its CVSS base score is 7.5 (High).

Operationally, ranked in the top 22.1% of CVEs by exploit likelihood; it is not currently listed in the CISA KEV catalog.

EU & UK References

Vulnerability details

Improper Input Validation vulnerability in Hitachi ABB Power Grids Relion 670 Series, Relion 670/650 Series, Relion 670/650/SAM600-IO, Relion 650, REB500, RTU500 Series, FOX615 (TEGO1), MSM, GMS600, PWC600 allows an attacker with access to the IEC 61850 network with knowledge of…

more

how to reproduce the attack, as well as the IP addresses of the different IEC 61850 access points (of IEDs/products), to force the device to reboot, which renders the device inoperable for approximately 60 seconds. This vulnerability affects only products with IEC 61850 interfaces. This issue affects: Hitachi ABB Power Grids Relion 670 Series 1.1; 1.2.3 versions prior to 1.2.3.20; 2.0 versions prior to 2.0.0.13; 2.1; 2.2.2 versions prior to 2.2.2.3; 2.2.3 versions prior to 2.2.3.2. Hitachi ABB Power Grids Relion 670/650 Series 2.2.0 versions prior to 2.2.0.13. Hitachi ABB Power Grids Relion 670/650/SAM600-IO 2.2.1 versions prior to 2.2.1.6. Hitachi ABB Power Grids Relion 650 1.1; 1.2; 1.3 versions prior to 1.3.0.7. Hitachi ABB Power Grids REB500 7.3; 7.4; 7.5; 7.6; 8.2; 8.3. Hitachi ABB Power Grids RTU500 Series 7.x version 7.x and prior versions; 8.x version 8.x and prior versions; 9.x version 9.x and prior versions; 10.x version 10.x and prior versions; 11.x version 11.x and prior versions; 12.x version 12.x and prior versions. Hitachi ABB Power Grids FOX615 (TEGO1) R1D02 version R1D02 and prior versions. Hitachi ABB Power Grids MSM 2.1.0 versions prior to 2.1.0. Hitachi ABB Power Grids GMS600 1.3.0 version 1.3.0 and prior versions. Hitachi ABB Power Grids PWC600 1.0 versions prior to 1.0.1.4; 1.1 versions prior to 1.1.0.1.

CWE(s)

Related Threats

No named actor attribution yet. ATT&CK technique mapping in progress for this CVE.

Affected Assets

hitachienergy
relion 670 firmware
1.1, 2.1 · 1.2.3 — 1.2.3.20 · 2.0 — 2.0.0.13 · 2.2.0 — 2.2.0.13
hitachienergy
relion 650 firmware
1.1, 1.2, 2.1 · 1.3 — 1.3.0.7 · 2.2.0 — 2.2.0.13 · 2.2.1 — 2.2.1.6
hitachienergy
relion sam600-io firmware
2.2.1 — 2.2.1.6
hitachienergy
rtu500 firmware
10.0, 11.0, 12.0, 7.0, 8.0
hitachienergy
reb500 firmware
7.3 — 7.60.19 · 8.2 — 8.2.0.5 · 8.3 — 8.3.1.0
hitachienergy
fox615 tego1 firmware
≤ r2a16
hitachienergy
modular switchgear monitoring firmware
≤ 2.1.0
hitachienergy
gms600 firmware
≤ 1.3.0
hitachienergy
pwc600 firmware
1.0 — 1.0.1.4 · 1.1 — 1.1.0.1

Mitigating Controls

Likely Mitigating Controls AI

Per-CVE control mapping for this CVE has not run yet; the list below is derived from the weakness types (CWEs) cited in the NVD entry.

addresses: CWE-20

Security testing and developer training directly verify and enforce proper input validation, reducing exploitability of injection and malformed-data weaknesses.

addresses: CWE-20

Security testing and evaluation at multiple SDLC stages directly detects missing or flawed input validation, with the required remediation process ensuring fixes are applied.

addresses: CWE-20

Directly implements checks on information inputs to reject invalid data before processing.

addresses: CWE-20

Spam protection mechanisms perform filtering and detection on inbound/outbound messages, directly compensating for missing or weak input validation of unsolicited content.

References