Cyber Resilience

CVE-2021-31884

Critical

Published: 09 November 2021

Published
09 November 2021
Modified
21 November 2024
KEV Added
Patch
CVSS Score v3.1 9.8 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
EPSS Score 0.0073 73.0th percentile
Risk Priority 20 60% EPSS · 20% KEV · 20% CVSS

Summary

CVE-2021-31884 is a critical-severity Improper Null Termination (CWE-170) vulnerability in Siemens Apogee Pxc Compact Firmware. Its CVSS base score is 9.8 (Critical).

Operationally, ranked in the top 27.0% of CVEs by exploit likelihood; it is not currently listed in the CISA KEV catalog.

EU & UK References

Vulnerability details

A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.4),…

more

APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.19), APOGEE PXC Modular (BACnet) (All versions < V3.5.4), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.19), Capital VSTAR (All versions with enabled Ethernet options), Desigo PXC00-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC00-U (All versions >= V2.3 and < V6.30.016), Desigo PXC001-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC100-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC12-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC128-U (All versions >= V2.3 and < V6.30.016), Desigo PXC200-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC22-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC22.1-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC36.1-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC50-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC64-U (All versions >= V2.3 and < V6.30.016), Desigo PXM20-E (All versions >= V2.3 and < V6.30.016), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.4), Nucleus Source Code (All versions), TALON TC Compact (BACnet) (All versions < V3.5.4), TALON TC Modular (BACnet) (All versions < V3.5.4). The DHCP client application assumes that the data supplied with the “Hostname” DHCP option is NULL terminated. In cases when global hostname variable is not defined, this may lead to Out-of-bound reads, writes, and Denial-of-service conditions. (FSMD-2021-0014)

CWE(s)

Related Threats

No named actor attribution yet. ATT&CK technique mapping in progress for this CVE.

Affected Assets

siemens
capital vstar
all versions
siemens
nucleus net
all versions
siemens
nucleus readystart v3
≤ 2017.02.1
siemens
nucleus source code
all versions
siemens
apogee modular building controller firmware
all versions
siemens
apogee modular equiment controller firmware
all versions
siemens
apogee pxc compact firmware
≤ 2.8.19 · ≤ 3.5.4
siemens
apogee pxc modular firmware
≤ 2.8.19 · ≤ 3.5.4
siemens
talon tc compact firmware
≤ 3.5.4
siemens
talon tc modular firmware
≤ 3.5.4
+13 more product configuration(s) — see NVD for full list

Mitigating Controls

No mitigating controls mapped yet. The per-CVE control annotator has not reached this CVE.

References