Cyber Resilience

CVE-2022-30313

High

Published: 28 July 2022

Published
28 July 2022
Modified
21 November 2024
KEV Added
Patch
CVSS Score v3.1 7.5 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N
EPSS Score 0.0027 50.3th percentile
Risk Priority 15 60% EPSS · 20% KEV · 20% CVSS

Summary

CVE-2022-30313 is a high-severity Missing Authentication for Critical Function (CWE-306) vulnerability in Honeywell Safety Manager Firmware. Its CVSS base score is 7.5 (High).

Operationally, ranked in the top 49.7% of CVEs by exploit likelihood; it is not currently listed in the CISA KEV catalog.

EU & UK References

Vulnerability details

Honeywell Experion PKS Safety Manager through 2022-05-06 has Missing Authentication for a Critical Function. According to FSCT-2022-0051, there is a Honeywell Experion PKS Safety Manager multiple proprietary protocols with unauthenticated functionality issue. The affected components are characterized as: Honeywell Experion…

more

TCP (51000/TCP), Safety Builder (51010/TCP). The potential impact is: Manipulate controller state, Manipulate controller configuration, Manipulate controller logic, Manipulate controller files, Manipulate IO. The Honeywell Experion PKS Distributed Control System (DCS) Safety Manager utilizes several proprietary protocols for a wide variety of functionality, including process data acquisition, controller steering and configuration management. These protocols include: Experion TCP (51000/TCP) and Safety Builder (51010/TCP). None of these protocols have any authentication features, allowing any attacker capable of communicating with the ports in question to invoke (a subset of) desired functionality. There is no authentication functionality on the protocols in question. An attacker capable of invoking the protocols' functionalities could achieve a wide range of adverse impacts, including (but not limited to), the following: for Experion TCP (51000/TCP): Issue IO manipulation commands, Issue file read/write commands; and for Safety Builder (51010/TCP): Issue controller start/stop commands, Issue logic download/upload commands, Issue file read commands, Issue system time change commands. A mitigating factor with regards to some, but not all, of the above functionality is that these require the Safety Manager physical keyswitch to be in the right position.

CWE(s)

Related Threats

No named actor attribution yet. ATT&CK technique mapping in progress for this CVE.

Affected Assets

honeywell
safety manager firmware
all versions

Mitigating Controls

Likely Mitigating Controls AI

Per-CVE control mapping for this CVE has not run yet; the list below is derived from the weakness types (CWEs) cited in the NVD entry.

addresses: CWE-306

Requires established identification and authentication to unlock, mitigating missing authentication for continued system access.

addresses: CWE-306

Requiring identification and rationale for actions allowed without authentication ensures critical functions are not left unprotected by forcing review of authentication requirements.

addresses: CWE-306

Authorizing mobile device connections to organizational systems ensures authentication is performed for this critical access function.

addresses: CWE-306

Guarantees critical functions are protected by mandatory invocation of the access control mechanism.

addresses: CWE-306

Auditing sessions makes it possible to detect access to critical functions without required authentication.

addresses: CWE-306

The assessment process confirms authentication is present and effective for critical functions, preventing exploitation from missing authentication.

addresses: CWE-306

Certification assesses that critical functions have required authentication controls in place.

addresses: CWE-306

Disabling non-essential functions and services eliminates the need to secure them, reducing exposure from missing authentication on unnecessary components.