CVE-2020-15795
Published: 22 April 2021
Summary
CVE-2020-15795 is a high-severity Out-of-bounds Write (CWE-787) vulnerability in Siemens Nucleus Net. Its CVSS base score is 8.1 (High).
Operationally, ranked in the top 27.8% of CVEs by exploit likelihood; it is not currently listed in the CISA KEV catalog.
EU & UK References
- 🇪🇺 ENISA EUVD: EUVD-2020-7778
Vulnerability details
A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20),…
more
Nucleus NET (All versions < V5.2), Nucleus Source Code (Versions including affected DNS modules), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS domain name label parsing functionality does not properly validate the names in DNS-responses. The parsing of malformed responses could result in a write past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to execute code in the context of the current process or cause a denial-of-service condition.
- CWE(s)
Related Threats
No named actor attribution yet. ATT&CK technique mapping in progress for this CVE.
Affected Assets
Mitigating Controls
Likely Mitigating Controls AI
Per-CVE control mapping for this CVE has not run yet; the list below is derived from the weakness types (CWEs) cited in the NVD entry.
Out-of-bounds writes that corrupt control flow or inject shellcode are rendered non-executable by the same memory protections.