Cyber Resilience

CVE-2022-38465

Critical

Published: 11 October 2022

Published
11 October 2022
Modified
21 November 2024
KEV Added
Patch
CVSS Score v3.1 9.3 CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H
EPSS Score 0.0015 36.0th percentile
Risk Priority 19 60% EPSS · 20% KEV · 20% CVSS

Summary

CVE-2022-38465 is a critical-severity Insufficiently Protected Credentials (CWE-522) vulnerability in Siemens Simatic Et 200 Sp Open Controller Cpu 1515Sp Pc2 Firmware. Its CVSS base score is 9.3 (Critical).

Operationally, ranked at the 36.0th percentile by exploit likelihood (below the median); it is not currently listed in the CISA KEV catalog.

EU & UK References

Vulnerability details

A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions…

more

< V21.9), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.5.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.9.2), SIMATIC S7-1500 Software Controller (All versions < V21.9), SIMATIC S7-PLCSIM Advanced (All versions < V4.0), SINUMERIK MC (All versions < V6.21), SINUMERIK ONE (All versions < V6.21). Affected products protect the built-in global private key in a way that cannot be considered sufficient any longer. The key is used for the legacy protection of confidential configuration data and the legacy PG/PC and HMI communication. This could allow attackers to discover the private key of a CPU product family by an offline attack against a single CPU of the family. Attackers could then use this knowledge to extract confidential configuration data from projects that are protected by that key or to perform attacks against legacy PG/PC and HMI communication.

CWE(s)

Related Threats

No named actor attribution yet. ATT&CK technique mapping in progress for this CVE.

Affected Assets

siemens
simatic et 200 sp open controller cpu 1515sp pc2 firmware
≤ 21.9
siemens
simatic et 200 sp open controller cpu 1515sp pc firmware
all versions
siemens
simatic drive controller cpu 1504d tf firmware
≤ 2.9.2
siemens
simatic drive controller cpu 1507d tf firmware
≤ 2.9.2
siemens
simatic s7-1200 cpu 12 1211c firmware
≤ 4.5.0
siemens
simatic s7-1200 cpu 12 1212c firmware
≤ 4.5.0
siemens
simatic s7-1200 cpu 12 1212fc firmware
≤ 4.5.0
siemens
simatic s7-1200 cpu 12 1214fc firmware
≤ 4.5.0
siemens
simatic s7-1200 cpu 12 1214c firmware
≤ 4.5.0
siemens
simatic s7-1200 cpu 12 1215fc firmware
≤ 4.5.0
+35 more product configuration(s) — see NVD for full list

Mitigating Controls

Likely Mitigating Controls AI

Per-CVE control mapping for this CVE has not run yet; the list below is derived from the weakness types (CWEs) cited in the NVD entry.

addresses: CWE-522

Training instructs users on protecting credentials from disclosure or unauthorized access.

addresses: CWE-522

Training records for security awareness and role-based training verify education on credential protection practices, tangibly reducing risks from mishandling or exposing credentials.

addresses: CWE-522

Protecting authenticator content from unauthorized disclosure and modification while requiring protective controls addresses insufficiently protected credentials.

addresses: CWE-522

Rules of behavior include credential protection and non-sharing requirements, reducing exposure of insufficiently protected credentials.

addresses: CWE-522

Terminating or revoking credentials stops use of insufficiently protected or lingering credentials post-termination.

addresses: CWE-522

Requiring confidentiality/integrity protection for stored credentials directly mitigates insufficiently protected credentials on disk or in configuration stores.

addresses: CWE-522

Credentials or keys delivered out-of-band are not exposed to interception or inadequate protection on the main transport.